Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 209
B-34
Parameters
1503-UM054C-EN-P – June 2013
Enhanced Module Hardware Output State
[IE Hardware Outputs]
Parameter Number:
62,50,38,26,14.
Access rule:
Get/Set
Data Type:
BYTE
Object Mapping:
0x4-2-3
Group:
Control
Units:
-
Minimum Value:
-
Maximum Value:
-
Default Value:
None
This parameter allows the user to view, as well as to control, the state
of the two (2) hardware output relays. Each bit position of the
parameter defines the state of one of the hardware outputs. If the bit
for a particular output is ‘0’ then that relay output will be Off but if
the bit is a ‘1’ then that relay output will be On.
Table B.5 – Enhanced Module Hardware Output States
Bit
Enum Text
Description
0
Bit 0: DLX Output A
Status of DeviceLogix Output A
1
Bit 0: DLX Output B
Status of DeviceLogix Output B
2
Unused
3
Unused
4
Unused
5
Unused
6
Unused
7
Unused
The outputs can each be toggled On or Off as shown in the following
RSNetworx screen in Figure B.1.
Defines the Power Source for the IE Board
[Current Power Source]
Parameter Number:
63,51,39,27,15.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x3-1-102
Group:
Control
Units:
-
Minimum Value:
0 = Power from DeviceNet
Maximum Value:
1 = Power from IB
Default Value:
0
This parameter allows the user to determine the source of operating
power for the IE board. This power can either be obtained from the
IB board or from DeviceNet.