Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 249
B-74
Parameters
1503-UM054C-EN-P – June 2013
TDUV Time Setting for IB2
[IB 2 TDUV Time]
Parameter Number:
134,114,94,74,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-2-50
Group:
Configuration
Units:
Seconds error in EDS file
Minimum Value:
0.2
Maximum Value:
2.0
Default Value:
0.2
This parameter allows the user to view and set the Time Delay
Undervoltage setting for the IB2 module. The Time Delay
Undervoltage setting is the time allowed for contactor IB2 to remain
operational when the mains input voltage goes below the minimum
operating voltage (see Electrical Specifications section for both
Close and Hold modes). See TDUV Programmability in Chapter 4
for a detailed description of this feature.
TDUV Time Setting for IB3
[IB 3 TDUV Time]
Parameter Number:
135,115,95,_,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-3-50
Group:
Configuration
Units:
Seconds error in EDS file
Minimum Value:
0.2
Maximum Value:
2.0
Default Value:
0.2
This parameter allows the user to view and set the Time Delay
Undervoltage setting for the IB3 module. The Time Delay
Undervoltage setting is the time allowed for contactor IB3 to remain
operational when the mains input voltage goes below the minimum
operating voltage (see Electrical Specifications section for both
Close and Hold modes). See TDUV Programmability in Chapter 4
for a detailed description of this feature.