beautypg.com

Mc operational troubleshooting procedures – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 172

background image

Troubleshooting 10-9

1503-UM054C-EN-P – June 2013

Table 10.C – IE Operational Trouble Shooting Procedures (cont.)

7-Segment

Display

State

Condition/Possible Cause

Corrective Action

6

flash

Fault

Incorrect MC R

TERM

installed

1. Incorrect R

TERM

selected

Set the R

TERM

resistor on only the last IntelliVAC MC

unit in an IntelliVAC MC system

L’+MC

address ‘1

flash

Fault

System lock-out state

Fault present, in MC system which will

not clear

Determine the fault that is occurring in the IntelliVAC

MC system and eliminate its source.

3

solid

Fault

Bad or no DeviceLogix program for MC

system

1. The Custom DeviceLogix module is

selected and has no program

entered.

2. The Custom DeviceLogix module is

selected and has errors.

Enter a valid program for the Custom DeviceLogix

module.

Correct any errors present in the Custom

DeviceLogix module.

7’+’DP

flash

Fault

Lost +15V rail from IntelliVAC Plus Basic

module

Input mains voltage is too low

Failed internal fuse

Faulty IntelliVAC Plus power supply

Check the mains input line and verify that it is

greater than the minimum operating level as defined

in the Electrical Specifications section in Appendix A.

For proper operation the input line must be greater

than 95Vrms to allow a contactor to be closed. If the

input voltage remains less than 95Vrms then

improvements to the source must be made.

Although the electronics in the IntelliVAC Plus and

IntelliVAC MC units will operate to a much lower

voltage level than 95Vrms, the contactor will not be

able to be closed at such

low levels.

Replace the internal fuse.

Replace the IntelliVAC Plus module.

8’+’DP

flash

Fault

Watchdog timeout – fatal error

Firmware crash occurred due to a faulty

microcontroller

Firmware crash occurred due to

excessive external EMI

Caused by a faulty microcontroller on the Enhanced

module. Replace the IntelliVAC Plus module.

Caused due to a high level of externally generated

EMI entering the wires connecting to the IntelliVAC

Plus module. Recycle the input power for both the

mains input as well as the DeviceNet power. If there

is no improvement then analyze the wiring to the

IntelliVAC Plus to determine if there is an unusual

amount of electrical noise present. If there is

excessive noise present, then rectify the situation. If

the unit still remains in a watchdog timeout fault then

replace the IntelliVAC Plus module.

MC Operational Troubleshooting Procedures

The following table identifies possible causes and corrective actions

when troubleshooting MC related faults using the IntelliVAC MC 7-

Segment LED Display.