Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 346

Parameters B-171
1503-UM054C-EN-P – June 2013
Contactor Coil Current for IB2
[IB 2 Contactor Coil Current]
Parameter Number:
331,273,215,157,_.
Access rule:
Get
Data Type:
FLOAT
Object Mapping:
0x384-2-61
Group:
Diagnostics
Units:
Amperes
Minimum Value:
00.000A
Maximum Value:
99.999A
Default Value:
00.000A
This parameter allows the user to view the real time operating Coil
Current for IB2. The current will be the Hold current for Electrically
Held contactors, only, because the Close/Trip coils for Mechanically
Latched contactors are only momentary currents and are not sustained
for extended time periods. See “Coil Currents” in Chapter 4 for a
more detailed description of this feature.
Contactor Coil Current for IB3
[IB 3 Contactor Coil Current]
Parameter Number:
332,274,216,_,_.
Access rule:
Get
Data Type:
FLOAT
Object Mapping:
0x384-3-61
Group:
Diagnostics
Units:
Amperes
Minimum Value:
00.000A
Maximum Value:
99.999A
Default Value:
00.000A
This parameter allows the user to view the real time operating Coil
Current for IB3. The current will be the Hold current for Electrically
Held contactors, only, because the Close/Trip coils for Mechanically
Latched contactors are only momentary currents and are not sustained
for extended time periods. See “Coil Currents” in Chapter 4 for a
more detailed description of this feature.