beautypg.com

GW Instek APS-1102 User Manual User Manual

Page 91

background image

4.4 Using the Sequence Function

APS-1102 Programmable AC/DC Power Source

4-27

f) Step synchronized output

The code that is specified in the step being executed is output to the external control I/O connector.
However, “0” is output during a normal output step.

Step 1

Step 2

Step 3

Step synchronized output

Time

Step 4

Step 5

0

1

[Step synchronized output]

0

1

0

0

1

Bit 0

Figure 4-10. Example of Step Synchronized Output


g) Step end phase setting

When the step end phase is set as enabled, the step execution time is as described below.

The step execution time = Set step time + Time for superimposed AC phase to become 0


After the set step time elapses, the setting for that step is retained in the subsequent operation.

Figure 4-11. Sequence Operation during Wait for Phase 0°

Value set for this step

Set value is
retained.

SWEEP

Time set by [step time]

Wait time for
0

 phase