10 adding external signals and internal signals – GW Instek APS-1102 User Manual User Manual
Page 125
4.10 Adding External Signals and Internal Signals
APS-1102 Programmable AC/DC Power Source
4-61
4.10 Adding External Signals and Internal Signals
When in the APS-1102 internal + external mode (AC-ADD, AC+DC-ADD), the internal signal source
signal can be added to the external signal input prior to output.
When using a signal input from an external source as a signal source, connect to the rear panel external
signal input/external sync signal input terminal (EXT SIG IN/EXT SYNC IN).
For this connection, use a coaxial cable with a BNC connector.
The input impedance is 10 kΩ (unbalanced), and the input frequency ranges from DC to 500 Hz.
See “4.9 Amplification of External Signal”.
For description of the External signal input/external sync signal input terminalspecifications:
See “3.3.4 External signal input/external sync signal input terminal”.
The setting ranges for output voltage and output frequency can be limited.
See “3.4.7 Using limiter functions”.
See “5.5.5 Setting range limiter (LIMIT)”.
Operation steps
Select
“output mode” in the SET menu, then select internal + external mode (AC-ADD and
AC+DC-ADD).
1. Press the
or
key to move the cursor to the
icon, then press the
ENTER
key.
The selection box is displayed.
ENTER
CANCEL
2. Press the
or
key to move the cursor to the mode to be set, then press the
ENTER
key.
This sets the selected output mode.
ENTER
CANCEL
Selection box