beautypg.com

5 operation principles – GW Instek APS-1102 User Manual User Manual

Page 20

background image

1.5 Operation Principles

APS-1102 Programmable AC/DC Power Source

1-6

1.5 Operation Principles

Figure 1-1 shows a block diagram of the APS-1102.

Figure 1-1. Block Diagram


The APS-1102 is broadly divided into four blocks.

<1> DC power source block

The DC power source block includes power factor improvement functions. The block provides DC
power sources for various devices on PCBs and for the amplifier block, while improving the power
factor of power supply input.


<2> Signal source and system control block

This block includes an internal signal source with sequence functions, and is able to provide
AC+DC output. It can also be used with added external inputs and internal signal sources. This
block also contains the user interface.


<3> Isolation block

The isolation block isolates the primary (main power source circuitry) and secondary sides.


<4> Amplifier block

The amplifier block includes a protection circuit.

PFC

CIRCUIT

LINE 100V-230V

50Hz/60Hz

1.4kVA MAX

POWER

LINE

FILTER

SUB-DCPS

CIRCUIT

<1> PFC

INVERTER

ISO

CIRCUIT

(PRI)

ISO

CIRCUIT

(SEC)

<3> ISOLATION

INVERTER

<4> AMP

INVERTER

OUTPUT
400Vpk MAX
1kVA MAX

CONTROL

I/O

USB

EXT SIG IN
2.2V MAX
Zin=10k


EXT SYNC IN
TTL

PANEL

<2> CONTROLLER

OSC

AMP

CONTROL

SYSTEM

CONTROL

DISPLAY

POWER

AMP

PROTECT

OUTPUT
AC250V MAX