6 example of sequence operation settings – GW Instek APS-1102 User Manual User Manual
Page 103
4.4 Using the Sequence Function
APS-1102 Programmable AC/DC Power Source
4-39
4.4.6 Example of sequence operation settings
The following describes the steps for setting a new sequence operation, based on the sequence transition
example described in Table 4-12. The time unit is seconds (s). (
See “5.6.5 Time unit setting”
to change the time unit.)
Figure 4-13. Step Transition Example (during AC+DC-INT mode)
Table 4-12. Program Settings
Step
Number
1 2 3 4 5 6
Step
time
(TIME)
0.1 0.2 0.1 0.2 0.2 0.3
DC voltage (DC VOLT)
25. 0
25. 0
75. 0
50. 0
100. 0
0.0
DC voltage operation type
SWEEP
KEEP CONST SWEEP SWEEP SWEEP
Step end (STEP TERM)
CONT
CONT
CONT
CONT
CONT
STOP
Jump step (JUMP STEP)
0
0
0
2
0
0
Jump times (JUMP NUM)
1
1
1
1
1
1
Branch
0
(BRANCH0)
0 0 0 0 6 0
Step
time
(TIME)
0.1 0.2 0.1 0.2 0.2 0.3
Since jump step = 2 has been set at step 4, a jump to step 2 occurs after step 4 is completed (<1> in Figure
4-13). At that time, a conflict exists between the step 2 settings, which are for both DC voltage value
(25.0 V) and DC voltage operation type (kept at 50.0 V), but since the operation type setting always takes
priority, only the DC voltage value = 50.0 V is valid.
Since jump times = 1 has been set, when step 4 is again completed after the jump, control switches to step
5 (<2> in Figure 4-13).
At step 5, step time = 0.2 s and DC voltage value = 100.0 have been set, but when trigger input occurs this
step control is transferred to step 6 (<3> in Figure 4-13).
Step 1
(0.1 s)
Step 2
(0.2 s)
Step 3
(0.1 s)
Step 4
(0.2 s)
Step 2
(0.2 s)
Step 3
(0.1 s)
Step 4
(0.2 s)
Step 5
(0.2 s)
Step 6
(0.3 s)
<1>
<2>
<3>
Time
Jump to step 2
“KEEP” setting
is valid.
Jump to step 6
upon external
trigger input.
100.0 V
75.0 V
50.0 V
25.0 V
0.0 V
Output
voltage
Setp 5 setting
value
Trigger input
Sequence start