GW Instek APS-1102 User Manual User Manual
Page 89

4.4 Using the Sequence Function
APS-1102 Programmable AC/DC Power Source
4-25
d) Sequence control
The following describes how sequence operations are controlled. Sequence control operations are 
indicated in triangular brackets (< >). 
Table 4-7. Sequence Control
Sets Run mode. 
When changing from Idle mode, the operation goes to step 1 when 
and the sequence is started. 
When changing from Hold mode, the sequence is resumed from where it was 
stopped when 
When 
the step specified by [jump step] when 
Changes from Run mode to Hold mode.
Changes to Idle mode. 
Immediately changes to normal output step. 
At that time, the values when 
[output parameter]. 
If the voltage or frequency setting when the 
limit, it is set to the lower limit value of the setting range limit. 
Changes to the step specified by [branch step]. 
Changes from the output at the time when 
Step 2 settings 
• Final value 
• Step time 
Step 1
Step 2
Time
Step 3
Output parameter
Figure 4-7. Example of Sequence Operation from Hold Mode to 
Step 1
Step 2
Step 5
Output parameter
Step 2 settings 
• Final value 
• Step time 
• Branch step 5 
Time
Step 5 settings 
• Final value from previous step is used 
Figure 4-8. Example of Sequence Operation at 
