Standard Drive Parameters

Appendix A

[Pr - 5.03]

Speed Window

Ultraware Name

Speed Functions: Speed Window

Description

If the speed error < Speed Window for 10 ms and the
Within Speed Window output signal is assigned, then the
Within Speed Window output is turned ON

Range

0…1000

Default

10

Units

Rotary motors: rpm; Linear motors: mm/s

When Enabled

Immediately

Applicable Operating Mode

Follower, Analog Velocity Input, Preset

Modbus Address

503

[Pr - 5.04]

Up to Speed

Ultraware Name

Speed Functions: Up to Speed

Description

If the motor speed > Up to Speed and the Up to Speed
output signal is assigned, then the Up to Speed output is
turned ON.

Range

1…5000

Default

20

Units

Rotary motors: rpm; Linear motors: mm/s

When Enabled

Immediately

Applicable Operating Mode

All

Modbus Address

504

[Pr - 5.05]

Zero Clamp

Ultraware Name

Speed Functions: Zero Clamp

Description

If the Analog Speed command < Zero Clamp, then the
Analog Speed command is ignored and the Motor Speed
command is set to zero.

Range

0…5000

Default

0

Units

Rotary motors: rpm; Linear motors: mm/s

When Enabled

Immediately

Applicable Operating Mode

All

Modbus Address

505