Appendix A

Standard Drive Parameters

Group 5 - Supplemental Drive Controls

[Pr - 5.00]

In Position Size

Ultraware Name

Position Functions: In Position Size

Description

If position error < In Position Size for 1 ms and the In
Position Size output signal is assigned, the In Position
output is turned ON.

Range

0…2500

Default

10

Units

Counts

When Enabled

Immediately

Applicable Operating Mode

Follower

Modbus Address

500

[Pr - 5.01]

Reserved

When Enabled

Reserved for future use.

[Pr - 5.02]

Near Position Size

Ultraware Name

Position Functions: Near Position Size

Description

If position error < Near Position Size and the Near Position
output signal is assigned, the Near Position output is
turned ON

Range

0…2500

Default

20

Units

Counts

When Enabled

Immediately

Applicable Operating Mode

Follower

Modbus Address

502