Rockwell Automation 2071-Axx Kinetix 3 Component Servo Drive Serial Host Command Reference Manual User Manual
Page 77

Rockwell Automation Publication 2071-RM001B-EN-P - April 2013
77
Standard Drive Parameters
Appendix A
[Pr - 1.30]
2nd Position Regulator Kp Gain
Ultraware Name
2nd Regulator Gain: Kp
Range
0…700
Default
20
Units
Hz
When Enabled
Immediately
Applicable Operating Mode
Position
Modbus Address
[Pr - 1.31]
2nd Current Command Lowpass Filter Bandwidth
Ultraware Name
2nd Regulator Gain: Low Pass Bandwidth (IReg)
Range
0…10,000
Default
300
Units
Hz
When Enabled
Immediately
Applicable Operating Mode
All
Modbus Address
[Pr - 1.32]
2nd Velocity Command Lowpass Filter Bandwidth
Ultraware Name
2nd Regulator Gain: Low Pass Bandwidth (VReg)
Range
0…10,000
Default
1000
Units
Hz
When Enabled
Immediately
Applicable Operating Mode
All
Modbus Address
[Pr - 1.33]
3rd Velocity Regulator P Gain
Ultraware Name
3rd Regulator Gain: P Gain
Range
0…10,000
Default
60
Units
-
When Enabled
Immediately
Applicable Operating Mode
Follower, Analog Velocity, Preset
Modbus Address