IAI America SSEL User Manual

Page 91

background image

69

Part 1 Installation

(2) Timing

chart

[1] Program start

[2] Program start by auto start

* Set input function specification value 5 (auto program start signal) for input port No. *.

[3] Soft reset signal

* Set input function specification value 3 (soft reset signal) for input port No. *.

[4] Servo ON signal

* Set input function specification value 4 (servo ON signal) for input port No. *.

[5] When the recovery type after emergency stop or enable operation is set to “Continued operation”

* Set “2” in other parameter No. 10, and set input function specification value 7 (operation-pause reset signal)
for input port No. *.
Set input function specification value 17 (drive-source cutoff reset input signal) for different input port No. *.

Ready output

Program
number input

External start
input

Program 1

Program 2

T1:

Duration after the ready output turns ON until input of
external start signal is permitted
T1 = 10 msec min.

T2:

Duration after the program number is input until input of
external start signal is permitted
T2 = 50 msec min.

T3:

Input duration of external start signal
T3 = 100 msec min.

Ready output

Auto program
start signal input

Auto program
start

T1:

Time after the ready output turns ON before the auto
program start signal can be input to input port No. *.
T1 = 10 msec min.

* Auto program start:

Set “0” in other parameter No. 7, “Auto program start
setting.”

Ready output

Soft reset
signal input

Program starting

T1:

Time after the ready output turns ON until input
function specification value 3 (soft reset signal) can be
input to input port No. *.
T1 = 10 msec min.

T2:

Time until the soft reset signal becomes effective.
T2 = 1 sec min.

T3:

Time after the soft reset signal is reset until the ready
signal is output.

Ready output

Servo ON
signal input

Servo ON

T1:

Time after the ready output turns ON until input
function specification value 4 (servo ON signal) can be
input to input port No. *.
T1 = 10 msec min.

T2:

Interval after the servo turns off until it turns on again.
T2 = 1.5 sec min.

Program starting

Emergency stop

Drive-source
cutoff reset

Pause reset

T1:

Time after the emergency stop input is reset until the
drive-source cutoff reset signal can be input.
T1 = 2 sec min.

T2:

Drive-source cutoff reset input time
T2 = 10 msec min.

T3:

Pause reset input time
T3 = 10 msec min.