beautypg.com

IAI America SSEL User Manual

Page 422

background image

400

Appendix

z Speed loop integral gain

Driver parameter number

Unit

Input range Default

value

(reference)

44

-

1 ~ 3276700

1667

This parameter determines the level of response with respect to a speed control loop.
Decreasing the value set in this parameter results in lower response with the speed command and decreases
the reactive force upon load change. If the setting value is low, compliance with the position command drops
and the positioning time increases as a result.
Increasing the setting value too much increases the tendency of the actuator to overshoot or oscillate,
resulting in increased mechanical vibration.

z Torque filter time constant

Driver parameter number

Unit

Input range Default

value

(reference)

45

-

0 ~ 2500

0

This parameter determines the filter time constant applicable to the torque command.
If the mechanical resonance frequency is equal to or lower than the servo loop response frequency, the
motor will vibrate.
This mechanical resonance can be suppressed by increasing the value set in this parameter.
It should be noted, however, that increasing the setting value too much may affect the stability of the control
system.

z Current control band number

Driver parameter number

Unit

Input range Default

value

(reference)

46

-

0 ~ 4

4

This parameter is used to change the current control band of a PI current control system.
The setting should not be changed in normal conditions of use.
Changing the parameter carelessly may affect the stability of the control system and a very dangerous
situation may occur.
Changing this parameter may be useful in some situations such as when resonance noise generates, in
which case a parameter change can help suppress the noise.
If you wish to change this parameter, please contact IAI.

Speed

Setting value is high (overshoot)

Setting value is low

Time