79

Part 1 Installation

OK Cancel

(4) Turn on the controller power.
(5) Start the PC software on a PC connected to the controller. From the Controller menu, select Absolute

Reset.

(6) When the Warning dialog box appears, click OK.

Warning

(7) The Absolute Reset dialog box appears.

(11) In the PC software window, click the Controller menu and then select Software Reset to restart the

controller.

Confirmation

(Note) If you continue to operate the controller without resetting the software or reconnecting the power,

the following errors may generate:
Error No. C70, ABS coordinate non-confirmation error
Error No. C6F, Home-return incomplete error

This completes the procedure to reset a battery voltage low alarm/error.

(8) Set the address number corresponding to

the axis whose battery has just been
replaced.
Note) Do not click Encoder Rotation Data

Reset 1.

(9) Click

Encoder Error Reset.

(10) Close the dialog box.

Absolute Reset