30 – appendix d: status and error messages, Messages on the log printer, Name table reconstructed – Gasboy CFN III Mgnr's Mnl V3.4 User Manual
Page 279

MDE-4315 CFN Series CFN III Manager’s Manual for Windows NT · August 2004
Page D-1
Appendix D: Status and Error Messages
30 – Appendix D: Status and Error
Messages
This chapter is divided into three sections:
• Messages on the log printer or in diagnostics.
• Messages in the transaction printout.
• Messages in command mode.
Messages within each section are listed alphabetically. If the first word of the
message may vary, it is listed at the beginning of the section.
Messages on the Log Printer
The following messages may appear on the log printer or terminal when it is in
log printer mode, or may be printed in response to the command PRINT
DIAGNOSTICS.
Name Table Reconstructed
Table name has been reconstructed because of an error. Some or all of the data
in the specified table may be missing.
The SC III will reboot itself to crashed state.
Call your service representative and report the table name.
You may use the appropriate print command to inspect the data. However, if the
Global table was reconstructed, the transaction data may still be there even
though it does not print out.
Do not restart the SC III until you have talked to a service technician. Then use
the command RUN;I to restart the SC III.
Switch the pumps to manual mode until the problem is fixed. Be sure to record
pump totalizer readings before switching the pumps to manual, than again after
the problem is solved and before switching back to automatic so fuel inventory
can be balanced. Follow your normal procedure for manually writing
proprietary-card transactions.
linename DSR not present
linename DSR regained
linename CTS not present
linename CTS regained