MDE-4315 CFN Series CFN III Manager’s Manual for Windows NT · August 2004

How To Do an Emergency Stop from the Terminal

You will probably never use this command unless a crisis arises. Use the command STOP;A to
terminate all pump transactions in progress and shut down the site.

The terminal will display the normal prompt when all transactions are paid off and the site is
shut down. Postpay transactions that were started from a console before the emergency stop
was executed need to be paid off if fuel has been pumped on them.

How To Do and Emergency Stop from the Console

On the Check Point, press DISABLE PUMPS.

On the Profit Point, press ALL STOP.

How To Restart a Site

Use the command RUN to restart the site if it was shut down with the command STOP or
STOP;A.

The RUN command will also restart the site from mild crashes, when no tables have been
reconstructed.

How To Restart from a Console Emergency Stop

If the site was shut down by pressing the console’s DISABLE PUMPS or ALL STOP key, the
site can be restarted by simply pressing the DISABLE PUMPS or ALL STOP key again. Use
the command RUN;A to restart the site if it was shut down by a console emergency stop and if
the site will not restart from the console.

The STOP;A command, DISABLE PUMPS and ALL STOP buttons at the cashier’s
station WILL NOT shut off electrical power to the pump/dispenser.

This means that even if you activate these stops, fuel may continue to flow
uncontrolled.

You must use the TOTAL ELECTRICAL SHUT-OFF in the case of an emergency and
not only these cashier station “stops.”

WARNING

!

P* STOP;A

Verify (y/n)? y

P*

RUN

P* RUN

Verify (y/n)? y

P*