Gasboy Q Series User Manual
Gasboy Hardware
020897 Rev. 06/12/03
Page 1
INSTALLING THE SUMP OVERFLOW CHECK VALVE
FOR Q SERIES SINGLE PUMPS
KIT #023900
023900 Kit Contents
Item
Part No.
Description
1
023997
Assembly, Sump Overflow Check Valve
2
020701
Vent Tube
3
020700
Assembly, Vent Tube
4
015191
Bracket, Sump Overflow
5
020702
Hanger, Conduit Size, 1-1/2"
6
051866
Screw, 1/4-20 x 1-1/4 HHC Pl
7
038860
Nut, 1/4-20 Hex
8
053919
Screw, 1/4-20 x 1/2 HH Taptite
9
026044
Fitting, 3/8 Elbow, Inverted Flared
10
058021
Grommet
11
020897
Instruction sheet (this sheet)
1. Turn off power to the pump. Unlock and open the doors. Trip the shear valve’s poppet to prevent fuel flow into
the pump.
2. Pre-assemble the conduit hanger (item 5) to the bracket (item 4)
using a ¼-20 x ½ Taptite screw (item 8). (NOTE: use the hole
that is ½” from the edge.) (Figure 1)
Figure 1
3. Slide the sump over flow assembly (item 1) into the conduit
hanger. Using the ¼-20 x 1-1/4 screw (item 6) and ¼” nut (item
7) to secure the sump over flow assembly loosely in place.
(Figure 2)
Figure 2