Plat-1004, Plat-1005, Plat-1006 – Brocade Network OS Message Reference v4.1.1 User Manual

Page 356

background image

340

Network OS Message Reference

53-1003227-01

PLAT-1004

8

PLAT-1004

Message

Turning off Fan because of airflow direction mismatch.

Message Type

LOG | FFDC

Severity

CRITICAL

Probable Cause

Indicates that the specified fan field-replaceable unit (FRU) has been turned off because it is
incompatible with the system airflow direction policy.

Recommended

Action

Replace the fan FRU. Refer to the Hardware Reference Manual of your switch for instructions to replace
the fan FRU.

PLAT-1005

Message

Unable to read EEPROM for Global airflow direction. Setting to default Port side

intake.

Message Type

LOG | FFDC

Severity

CRITICAL

Probable Cause

Indicates a failure to read the electrically erasable programmable read-only memory (EEPROM) to
determine the airflow direction of the fans. Therefore, setting the airflow direction to be from the port side
of the system.

Recommended

Action

Execute the copy support command and contact your switch service provider.

PLAT-1006

Message

Unable to read EEPROM for Global airflow direction. Shutting off Fans now.

Message Type

LOG

Severity

CRITICAL

Probable Cause

Indicates a failure to read the electrically erasable programmable read-only memory (EEPROM) to
determine the airflow direction of the fans. The fans will be shut down.

Recommended

Action

Execute the copy support command and contact your switch service provider.