TABLE N1. MINIMUM DATA SET FROM BUILDING EQ

Item

Measured value

unit

time

resolution*

remarks

consumption

total consumption of natural gas

kWh

h

natural gas

Total consumption of fuel oil

kWh

h

Fuel oil

total consumption of district heat

kWh

h

total consumption of district cold

kWh

h

total consumption of electricity

kWh

h

total consumption of water

h

weather

outdoor air temperature

°C

h

own weather station or from weather data provider

outdoor rel. humidity

%

h

own weather station or from weather data provider

global irradiation

W/m²

h

own weather station or from weather data provider

Indoor conditions

indoor temperature

°C

h

choose one or more reference zones for that measurement

indoor relative humidity

°C

h

choose one or more reference zones for that measurement

System

Flow / return Temperatures of
main water circuits

°C

h

main heat/cold distribution.
”Main” in this context refers to the distribution in the building
and not to a primary distribution such as a district heating system.

supply air temperature of main
AHUs

°C

h

only if supply air is thermodynamically treated

supply air relative humidity of
main AHUs

%

h

only if supply air is humidifi ed / dehumidifi ed

* h = hourly

TABLE N2. DESIRABLE ACCURACY OF DATA POINTS

Measurement Point or Metric

Accuracy Goal

Outside ambient temperature (°F)

.2 °C

Outside ambient wet bulb temperature (°F)

.2 °C

Zone temperature (°F)

.5 °C

HVAC electric only energy use (kWh)

1.5% of reading

Chilled, hot water temperature (°F)

.1 °C, if >= 5 °C delta T

Chilled, hot water delta temperature (°F)

2% of reading

Chilled, hot water fl ow (gpm)

2% of reading, > 20–1 turndown

Natural gas fl ow (scfm)

2% of reading, > 10–1 turndown, w/ pressure and temperature compensation; Using an
average heat content of the gas to convert to kBtu introduces a –2% error

Air fl ow (cfm)*

5% of reading down to 10% of full scale, > 10–1 turndown

Power (kW)

2.0% of reading

Chiller cooling output (tons)

3% of reading

Chiller cooling energy (ton-hrs)

3% of reading

Boiler heating output (kBtu/hr)

3% of reading

Boiler heating energy (kBtu)

3% of reading

Electric energy use (kWh)

2.0% of reading

Total HVAC energy use (kWh) (inculdes air side, water
side and natural gas)

3% of reading

Chiller performance (kW/ton)

4% of reading

ChW Plant performance (kW/ton)

4% of reading

Total boiler performance (kBtuo/kBtui) (COP)

4% of reading

Total air handler performance (kW/cfm)

6% of reading

Net Usable Building fl oor area

2%