J8 ENERGY & PROCESS ASSESSMENT PROTOCOL

72%

30400

108160

25%

64%

81250

227500

50%

56%

148330

340795

75%

52%

219240

460013

100%

HEDS %

energy

savings

High efficiency dehumidification

system (HEDS)

chiller plant load + reheat

energy (BTUH)

Normal AHU system

chiller plant load + reheat

energy (BTUH)

% design CFM

55

68.1

63

75

25%

55

67.2

64

76

50%

55

65.7

64.5

77

75%

55

65.1

65

78

100%

Dew point

DB

WB

DB

% design CFM

Leaving conditions

Entering conditions

Normal HVAC vs. HEDS

TABLE J1. VARIABLE VOLUME SYSTEM PERFORMANCE COMPARISON

28%

1126150

1561813

45°F

HEDS %

energy

savings

High efficiency dehumidification

system (HEDS-DOAS)

chiller plant load + DX

subcooling + reheat energy

(BTUH)

Chiller plant load + DX

subcooling + reheat energy

(BTUH)

CHWS

temperature

at unit

45

65

82

98

45°F

Dew point

DB

WB

DB

CHWS

temperature

at unit

Leaving conditions

Entering conditions

Normal DOAS vs. HEDS-DOAS

TABLE J2. DEDICATED OUTDOOR AIR SYSTEM (DOAS) PERFORMANCE COMPARISON

High efficiency dehumidification system : Energy savings @ 100% Reheat to 65 F/68 F

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

1

2

3

4

Percent of design airflow

Percent of cooling and reheat energy saved

Figure J7. High Effi ciency Dehumidifi cation System: Energy Savings Vs. Design Air Flow @ 100%
reheat to 65F/68F – Typical for DOAS used for barracks, labs, manufacturing facilities, etc.