Retrotec DM-2 DucTester setup for Codes User Manual

Setup ductester gauge for codes, Quickguide

background image

QG135

Page 1 of 2

rev-2012-08-29

QuickGuide

Setup DucTester gauge for Codes

(referencing 2009 IECC)

● Press the [On/Off] key.

● Press [Exit] to get to

the main screen.

● Press [Setup].

● Press [

] until “Device Setup” is highlighted.

● Press [Enter].

The screen will now display all of the different types

of equipment that can be used with the DM-2.

To eliminate Devices not relevant to

duct testing, follow the steps

outlined below.

● Scroll down the list of Devices, one by

one, by pressing [

] .

● Select “No” for all Devices except “Retrotec DU200”.

Scroll down, one by one, and turn the other devices

to “No” by pressing [

].

● Now press [Exit] to return to the

“Setup” menu.

The gauge will now only display “Retrotec DU200”

on the main screen. If you want to use this gauge

for other Devices, select “Yes” for that Device on the

“Enable/Disable Device” menu.

Step 1:

Setup for Device

Step 2:

Setup Device Choices

This is what your gauge should look like before you begin

testing ducts. The following steps will show you how to

easily setup your gauge for duct testing to code

standards (

the 2009 IECC - International Energy Conservation Code

).

Code Required

Results

Correct Device

Range Configurations: It is recommended

to start on the Mid-Range Ring.

“No” means that the Device will not

display on main screen, “Yes” means

that it will display on the main screen.