beautypg.com

Retrotec USACE User Manual

Page 380

background image

J4 ENERGY & PROCESS ASSESSMENT PROTOCOL

Temp
scale

kW/ton
scale

Condenser water return temperature

Condenser water supply temperature

Chiller kW per ton of cooling

Chilled water supply temperature

Chilled water return
temperature

Figure J2. Example of Load-Based Optimization System (LOBOS) reset strategies in operation.

This test was run to see what effects changing the condenser water tem-

perature setpoint would have on VFD chiller system effi ciency.
The red line is the condenser water temperature with a system using

the Load-Based Optimization System (LOBOS) control system, which
determines less wasteful, more effi cient operating points for the heat-
ing, ventilating, and air-conditioning (HVAC) system based on the
actual cooling loads of the facility.
The blue line is the chiller effi ciency in kW per ton.

The green line is the chilled water supply temperature.

The test shown in the trend log screenshot shows that the chiller

energy effi ciency is running at approximately 0.33 kW per ton prior to
the start of the test.
This is excellent effi ciency, as most chillers installed today operate

between 0.60 and 1.5 kW per ton of cooling.
With LOBOS, the condenser water temperature is running at approxi-

mately 20 °C (68 °F), while the chilled water temperature is running at
approximately 10 °C (50 °F).
We manually raised the condenser water setpoint to 26.7 °C (80 °F)

from the automatically controlled setpoint of 68 °F to determine what
effect a “normal” operating strategy would have on chiller system per-
formance. Many facilities routinely operate their condenser water sys-
tems at between 26.7 and 29.4 °C (80 and 85 °F), the typical “design”
points for chillers when they leave the chiller factory.
As can be seen, the chiller effi ciency was made dramatically worse

when the CHWS temperature was raised by 11.1 °C (12 °F), increas-
ing from 0.33 kW per ton to 0.45 kW per ton, using 36% more energy