beautypg.com

G.14.5 heating system measurements, G.14.6 other measurements, G.14.7 questionnaire – Retrotec USACE User Manual

Page 359: G.14.8 document study

background image

Appendix G G29

G.14.5 Heating System Measurements

Water fl ow measurements and temperature measurements of heat

exchanger (two to three days, minimum, are needed)
Water fl ow can be measured by clamp-on meters (ultrasonic method;

also, pipe wall thickness must be measured)
Measurements of selected radiators (surface temperature distribution,

incoming and outgoing water fl ow measurements)

G.14.6 Other Measurements

Heat-fl ux measurements to determine the U-value of certain building

parts
Draft measurements using smoke and precision direction-free (3-D)

thermoanemometer
Globe-temperature measurements by globe thermometer

G.14.7 Questionnaire

A questionnaire to map user’s comments and opinions

Interviews of operating staff, janitors

G.14.8 Document Study

Consumption fi gures, benchmarking (comparison with similar build-

ings and the history of that particular building), and so on; comparison
to weather data is a source of more reliable information about building
conditions and material properties.