TABLE 4. CAUSES OF ENERGY WASTE AND INEFFICIENCY IN CENTRAL ENERGY PLANT

AND DISTRIBUTION SYSTEMS (Continued)

Problem description

Waste/ineffi ciency

Reference/appendix

Boiler
systems

Leaking steam traps

Waste

D4.1.4

(

continued)

Overventing the deaerator

Ineffi ciency

D4.1.5

Poor water treatment

Ineffi ciency

D4.1.6

Excessive heat losses due to poor pipes insulation

Waste

D4.1.7

Dirty burners

Ineffi ciency

D4.1.8

Improper operating dampers

Ineffi ciency

D4.1.9

Inoperable, uncalibrated, or poorly adjusted controls

Ineffi ciency

D4.1.10

Boiler tubes not cleaned in two years

Ineffi ciency

D4.1.11

Damaged or missing refractory

Ineffi ciency

D4.1.12

Combustible gases in the fl ue exhaust

Ineffi ciency

D4.1.13

Excessive venting of steam

Waste

D4.1.14

Steam pressure greater than required by processes

Ineffi ciency

D4.1.15

Steam line serving unused areas

Waste

D4.1.16

More than 20% excess oxygen in fl ue gases

Ineffi ciency

D4.1.17

Flue gases warmer than 66 °C (150 °F) leaving hot wa-
ter or steam temperature

Waste

D4.1.18

Blowdown water warmer than 60 °C (140 °F)

Waste

D4.1.19

Use of dampers to control air fl ow

Ineffi ciency

D4.1.20

Surface temperature of boiler, pipes, or other hot sur-
faces greater than 52 °C (125 °F)

Waste

D4.1.21

Use of continuously lit pilots

Waste

D4.1.22

Boiler cycling on and off at low loads

Ineffi ciency

D4.1.23

Vent gases released outdoors warmer than 93 °C (200 °F)

Waste

D4.1.24

Use of small ineffi cient steam turbines (less than 65%)

Ineffi ciency

D4.1.25

Use of cooling tower or river water to condense steam
turbine exhaust steam

Waste

D4.1.26

Use of pressure-reducing valve to provide pressure
reductions

Ineffi ciency

D4.1.27

Use of a boiler having an effi ciency less than 70%

Ineffi ciency

D4.1.28

Use of steam to atomize oil

Ineffi ciency

D4.1.29

Use of ineffi cient burners

Ineffi ciency

D4.1.30

Fuel oil too cold for good atomization

Ineffi ciency

D4.1.31

No automatic stack damper

Waste

D4.1.32

Boiler location remote from area served

Ineffi ciency

D4.1.33

Energy Conservation Measures 79