beautypg.com

H.8 cooling energy consumption, Where – Retrotec USACE User Manual

Page 366

background image

H6 ENERGY & PROCESS ASSESSMENT PROTOCOL

t

w

= operation time of ventilation system/week, days/7 days

Q

HR

= utilized heating energy recovered from exhaust air by heat recovery

equipment, kW

H.7 Heating Energy Consumption due to Infi ltration

Q

inf

=

* C

p

* n

inf

* V * 24 * S / 3600

where

Q

inf

= heating energy consumption due to infi ltration, kWh

= air density, kg/m

3

C

p

= heat capacity of air, kJ/(kg * °C)

n

inf

=

infi ltration airfl ow, air changes per hour, ACH or (m

3

/h)/m

3

V

= building volume, m

3

24 =

coeffi cient converting degree days to degree hours, hr/day

S

= heating degree days, °C * days

3,600 = coeffi cient converting hr into sec

H.8 Cooling Energy Consumption

Q

cool

= 24 BLC * CDD / COP

where

Q

cool

= cooling energy consumption, kWh

24 =

coeffi cient converting degree days into degree hours

BLC = building loss coeffi cient, W/°C

CDD = cooling degree days, °C * days

COP = coeffi cient of performance of air conditioner

The accuracy of a building energy balances depends on many factors, in-

cluding the accuracy of measuring devices, number of measurement points,
duration of measurements, and so on, but shall be better than 5–5%, depend-
ing on the size of the facility. When computing an energy balance, it is neces-
sary to pay attention to operating modes of systems and the process equip-