beautypg.com

Dc link reactor – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control (PanelView 550) User Manual

Page 92

background image

92

Rockwell Automation Publication 7000-UM151E-EN-P - January 2013

Chapter 3 Component Definition and Maintenance

The iron core of the DC link has thermal protection.

Above the DC link is the main drive cooling fan. The primary elements of the fan
are the inlet ring, impeller and motor. The inlet ring is stationary and must not
contact the rotating impeller.

An air exhaust hood is mounted on top of the cabinet; ensure you install it
correctly to prevent foreign objects entering the drive. If there is a redundant fan
option, it is mounted on the top of this cabinet, inside an enlarged exhaust hood.

DC Link Reactor

The DC Link maintains a ripple-free current between the rectifier and the
inverter. The link design ensures that it cools with air drawn through its coils.

The DC link reactor does not normally require service. In the event of its
replacement, however, Rockwell Automation must approve the replacement link.

To service the DC link, see

Figure 69 on page 93

.

1. Lock out the drive’s source power.
2. Open the DC link cabinet door and remove the screws holding the vertical

sheet metal barrier in front of the DC link.

3. The DC link is equipped with flexible power leads. Disconnect the 4

power connections.

4. Remove the horizontal barrier around the DC link.
5. Remove the hardware that secures the DC link to the floor channel.
6. Disconnect the ground connection.