Chapter 5 Drive Programming and Parameters

Initialize

The drive contains a default set of parameters and operational information that
form the basis for drive configuration. To initialize the drive with the default
data, press [F3] on the top-level menu.

Figure 208 - Initialize operation

When prompted to confirm the operation, press [F8] to proceed or [F9] to abort.
Initialization overwrites the data currently in the drive, but does not affect
previous changes saved to NVRAM.

Save

Save the drive configuration changes if you do not want to lose the data when the
drive powers off. To save the changes, press [F5].

Figure 209 - Save operation

To confirm the operation, press [F8] to proceed or [F9] to abort. Saving the data
overwrites any previously-stored data in the NVRAM.