15. Click Start. HyperTerminal now acts as a dummy printer and waits for the
information to be transmitted from the drive to the laptop.
16. On the drive terminal, press [F3] (PRINT) at the main screen as shown
below.
Figure 147 - Printing to HyperTerminal from the drive interface
17. The terminal displays the Printer options, as shown below. Use
▲
or
▼
to
scroll to the item you want to print (i.e., upload the info into laptop) and
press Enter. The drive will print the selected information to your laptop
through the specified file (in this example, C:\temp\Example.txt). Repeat
this step to upload any other data into your laptop.
The most common downloadable selections are:
• Drive Setup: for complete setup including parameters, fault masks and
revisions
• Trend Data: for analyzing the drive trending
• Variables: snapshot of real-time operational data
18. Stop the communication between your laptop and the drive and close the
file Example.txt. On the laptop, click on Transfer menu and select Stop
option under Capture Text … as shown in the screenshot below.
IMPORTANT While the data is being transferred, the Printer Status will show Transfer
in Process. Once the data transfer is complete, the Printer Status
changes to either Auto-Off or Auto-On.