Chapter 3 Component Definition and Maintenance

Figure 18 - Transient Suppression Network

Replacing Metal-Oxide Varistors

Metal-oxide varistors (MOV) are part of the TSN located within the connection
cabinet.

1. Ensure there is no power to the equipment.

2. Observe the locations of the connecting links.
3. Detach the connecting links by removing the screws.
4. Using a screwdriver remove the screws at the base.
5. Replace the MOV (polarity is not an issue).
6. Continue by replacing the screws and connecting links.

7.2 kV fuses

5 kV fuses

Varistors

Location of ground

Connecting links

Varistors

Location for 7.2 kV fuses

Location for 5 kV fuses

ATTENTION: To prevent electrical shock, disconnect the main power
before working on the drive. Verify that all circuits are voltage-free using
a hot stick or appropriate voltage-measuring device. Failure to do so may
result in injury or death.