Component Definition and Maintenance Chapter 3

7. Remove the Drive Processor Module from the four, 34-pin female

connectors and one, 16-pin female connector on the ACB.

8. Remove the DIM module from the DPM and plug it on the new DPM

before replacing the DPM.

9. Reverse steps 7 – 3 to re-install the boards into the low voltage control

cabinet.

10. Apply control power to the drive. The DPMs ship without installed

firmware, so the drive will shift into download mode. Install firmware in
the drive following the guidelines the Installation Manual.

11. Program the drive. Refer to Technical Data “Medium Voltage AC Drive

Parameters” – Publication 7000-TD002_-EN-P. Save the parameters to
NVRAM and externally, using the options described earlier in this section.