beautypg.com

Replacing a dc/dc power supply – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control (PanelView 550) User Manual

Page 115

background image

Rockwell Automation Publication 7000-UM151E-EN-P - January 2013

115

Component Definition and Maintenance Chapter 3

Replacing a DC/DC Power Supply

Figure 88 - Replacing a DC/DC power supply

1. With the drive energized, check that all output voltages are present (view

1).

2. De-energize the drive, isolate and lock out the control power, and remove

all wire connections from the unit (view 1).

3. Remove four (4) M6 (H.H.T.R.S.) so you can remove the DC/DC power

supply assembly from the low voltage panel (view 1).

4. Remove four (4) M4 (P.H.M.S.) and nylon shoulder washers from the

back of the mounting plate (view 2)

9

+5V_PWR (+5V,5A)

+5V,5A/com1

10

DGND (com1)

0V/com1

11

EARTH

earth ground

P4 – PWR (To

ACB)

PIN NO.

LABEL

DESCRIPTION ONLY

M4 (P.H.M.S.) and

nylon shoulder washer

Mounting Plate

Black Insulation

DC/DC

power supply

Part ID Label

M6 (H.H.T.R.S.)

VIEW “1”

VIEW “2”