Calculate the capacitance using the first reading. In this case:

Similarly, you can calculate the capacitance for the remaining two measurements
for L2-N and L3-N.

Converter Cabinet

Components

This section describes the converter cabinet components of your PowerFlex 7000
“B” Frame drive. It also details a number of regular or recurring maintenance tasks
that will keep your drive in peak operating condition.

For control/cabling cabinets, see

Control / Cabling Cabinet Components on

page 23

.

For DC link/fan cabinets, see

DC Link and Fan Cabinet Components on

page 88

.

V = 200V, I = 1.87 for L1-N
Xc = V/I = 200/1.87 = 106.95
C= 1/ (2

π

F Xc)

C= 1/(2 x 3.14 x 50 x 106.95
C=29.7μ

F