Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control (PanelView 550) User Manual
Page 119
![background image](/manuals/580207/119/background.png)
Rockwell Automation Publication 7000-UM151E-EN-P - January 2013
119
Component Definition and Maintenance Chapter 3
Table 1 - Test Points on Drive Processor Module
This table defines the states of LEDs D9 and D11 on the DPM board, which uses
D9 for the Inverter side processor, and D11 for the Rectifier side processor. The
other two LEDs (D6 and D7) are the watchdogs for the Inverter and Rectifier
code respectively.
Table 2 - Description of D6 and D7 Function
Table 3 - Description of D9 and D11 Function: Boot Code Status
Test points
Name
Description
DPM-TP1
+1.2V
+1.2V DC power supply
DPM-TP2
+1.8V
+1.8V DC power supply
DPM-TP3
+2.5V
+2.5V DC power supply
DPM-TP4
+3.3V
+3.3V DC power supply
DPM-TP5
+5V
+5V DC power supply
DPM-TP6
DGND
Digital ground
DPM-TP7
ITP1
Digital to Analog output – Assignable diagnostic test point
DPM-TP8
ITP2
Digital to Analog output – Assignable diagnostic test point
DPM-TP9
ITP3
Digital to Analog output – Assignable diagnostic test point
DPM-TP10
ITP4
Digital to Analog output – Assignable diagnostic test point
DPM-TP11
RTP1
Digital to Analog output – Assignable diagnostic test point
DPM-TP12
RTP2
Digital to Analog output – Assignable diagnostic test point
DPM-TP13
RTP3
Digital to Analog output – Assignable diagnostic test point
DPM-TP14
RTP4
Digital to Analog output – Assignable diagnostic test point
Color
Rate or Count (Pulse) Meaning
Green
Solid
Application firmware is running
Color
Rate or Count (Pulse) Meaning
Green
10 Count
PreExecution OK
Red
.25 Hz
No Bootcode
Green
.25 Hz
No Application
Green
.5 Hz
Downloading via Serial Port
Green
2 Hz
Serial Port Active – i.e. Terminal
Green
1 Hz
Waiting/Loading Application
Green
Solid
Application Running
Red
Solid
Operation Failed
Red
2 Count
POST – RAM Failed
Red
3 Count
POST – NVRAM Failed
Red
4 Count
POST – DPRAM Failed
Red
8 Count
FPGA Loading Failed