Component Definition and Maintenance Chapter 3

Press [F10] (Access), and select Advanced. Press [Enter], or enter the password (if
prompted) for Advanced access.

Figure 105 - Operator Interface terminal access

Press [F10] to Exit, then [F5] for NVRAM. Press [F5] again to SAVE, and [F8]
for YES. The drive should save the parameters to NVRAM. Press [F10] again to
EXIT.

Figure 106 - Operator interface — save to NVRAM

To save to the Operator Interface Terminal and Flash Card, Press [F2]
(UTILITY), [F7] (TRANSFER), and [F4] (PARAMETERS). You should now
see the following screen:

Figure 107 - Operator interface — transfer parameters

To save parameters to the Operator Interface Terminal, press [F5] (DRV>MEM).
To save to the Flash Card, insert the card in the terminal. Remove the back cover