beautypg.com

Downloading drive processor firmware, Overview – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control (PanelView 550) User Manual

Page 146

background image

146

Rockwell Automation Publication 7000-UM151E-EN-P - January 2013

Chapter 3 Component Definition and Maintenance

Downloading Drive

Processor Firmware

All PowerFlex 7000 Medium Voltage drive control functions are loaded on the
Drive Processor Module (DPM) with firmware via a serial connection on the
Drive Processor Module data port J4. The firmware is packaged into a single
executable file (with the extension .exe).

This section describes how to download new or updated firmware to the drive
using the DPM data port. The drive stores downloaded firmware in non-volatile
Flash memory.

The latest firmware and the associated release notes are available on the Medium
Voltage intranet site, or can be obtained from Medium Voltage Product Support.

Overview

When you power up the system, the drive executes the Application Code
contained in the on-board flash memory. If it does not have valid firmware, then
the entire system shifts into a download mode to await a firmware download via
the serial data port J4 on the DPM.

You can also force the download mode from the drive terminal if you have
‘ADVANCED’ access privileges for the drive. If you have the relevant secure PIN
for that access, select UTILITY-TRANSFER-SYSTEM on the terminal to put
the drive into download mode.

Ensure you save the current drive parameters to NVRAM, to the Operator
Interface Terminal, and to any other external source such as the Flash Card,
DriveTools, or printed to a hardcopy.

TP34

DIAG_14

OIB C, RX3 Diagnostic Feedback

TP35

CMD_14

OIB C, TX3 Firing Command Signal

TP36

DIAG_15

OIB C, RX4 Diagnostic Feedback

TP37

CMD_15

OIB C, TX4 Firing Command Signal

TP38

DIAG_16

OIB C, RX5 Diagnostic Feedback

TP39

CMD_16

OIB C, TX5 Firing Command Signal

TP40

DIAG_17

OIB C, RX6 Diagnostic Feedback

TP41

CMD_17

OIB C, TX6 Firing Command Signal

TP42

TFB_C

OIB C Temperature Feedback Signal – There is no provision in

the drive for the use of this signal, it is only provided for

Rockwell internal testing.

TP43

GND

Ground Reference for TP30 – TP42

Test Point

Signal Name

Description