Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control (PanelView 550) User Manual

Page 257

background image

Rockwell Automation Publication 7000-UM151E-EN-P - January 2013

257

General Reference Appendix A

Table 11 - PowerFlex Speed Regulation

Notes:

• Speed regulation is based on a percentage of motor synchronous speed.
• Tachometer to be mounted on the AC machine
• Operational 15 V DC Power Supply mounted in drive to power the

tachometer as a standard option with the tachometer feed back card.

• Customer is responsible for providing and mounting of tachometer
• Sleeve bearing motors require the tachometer to have an axial movement

tolerance.

• Recommended tachometers are shaft mounting type.
• Magneto resistive models are more adaptable to harsh environments.
• When installing, the tachometer body and electronics must be isolated

from ground (options available from the tachometer manufacturer to
accomplish this).

• There are usually limits on tachometer cable lengths. Ensure the maximum

length is suitable for the application.

Tachometer

Frequency Output

<6 Hz

6-15 Hz

>15 Hz

Without Tachometer

Not applicable

0.1%

0.1%

With Tachometer

0.02%

0.01%

0.01%

Recommended Tach PPR

Motor RPM

Tach ppr

3600

600

3000

600

1800

1024

1500

1024

1200

2048

1000

2048

900

2048

720

2048

600

2048