Appendix B Line & Load Cable Sizes

Notes:
This data is informative only; do not base final design criteria solely on this data. Ensure you follow

national and local installation codes, industry best practices, and cable manufacturer

recommendations.

1. Some ‘A’ Frames, most ‘B’ Frames, and all ‘C’ Frames have a single enclosure opening provision for

both line and load cables (designated by

1

).Most ‘A’ Frames and some ‘B’ Frames have separate

opening provisions for line and load cables. All cabling capacities shown in this table are “worst

case” conditions when both line and load cabling enters and exits in the same direction.

2. Cable sizes are based on overall dimensions of compact-stranded three-conductor shielded cable

(common for industrial cable tray installations). Maximum sizing stated accounts for minimum rated

cable insulation requirements and the next higher-rated cable (i.e., 8kV is not commercially available

in many areas of the world, therefore Rockwell Automation provides an 8kV (minimum rating) as

well as a 15kV rating, when applicable. Enclosure openings will accommodate the thicker insulation

on the higher-rated cable. IEC ratings show the equivalent to the NEMA sizes. The exact cable mm

2

size shown is not commercially available in many cases; use the next smaller standard size.

3. Cable enters termination point horizontally in this case, therefore orient space for the stress cones

horizontally also.

4. Minimum cable bend radius recommendations vary by national codes, cable type, and cable size.

Consult local codes for guidelines and requirements. General relationship of cable diameter to bend

radius is typically between 7x —12x (e.g., if the cable diameter is 1 inch [2.54cm] the minimum bend

radius could range between 7-12 inches [18.8-30.48cm]).

5. For minimum cable insulation requirements, refer to the “PowerFlex 7000 Medium Voltage AC Drive

User Manual” for your particular frame (‘A’, ‘B’, or ‘C’ Frame). Stated voltages are peak line-to-

ground. PLEASE NOTE: Some cable manufacturers rate cabling based on RMS line-to-line.

6. Ground lug capabilities: ‘A’ Frame—two (2) mechanical range lugs for ground cable connections; ‘B’,

or ‘C’ Frame—up to ten (10) mechanical range lugs for ground cable connections are available,

typically these frames supply four (4). Mechanical range lugs can accommodate cable size #6-

250MCM (13.3 - 127mm2).

7. 18 Pulse VFDs (R18TX) have nine (9) line-side connections from the secondary isolation transformer

windings entering the VFD. Lug pads are available for each connection. The lug pad and enclosure

can generally accommodate 2 cables per connection, 18 cables in total (applies to all “B” and “C”

configurations).

8. Maximum cable size for “B” Frame (2 per phase) and “C” Frame (4 per phase) is 500MCM (253mm

2

,

limited by lug pad assembly size and clearance requirements.

9. As cabling methods can vary widely, maximum cable sizes shown do not account for the size of the

conduit hub. Verify size of conduit hub(s) against the “Drive enclosure openings” shown.

‘B’ Frame

(Air-

Cooled)

cont’d.

PF7000

2400V/60Hz/RP18TX

7

46-430

70.8

9.79x21.06 (249x535)

1

(2) 500MCM 5kV

or 8kV/phase

(2) 253mm² 5kV

or 8kV/phase

16.4 (415)

PF7000

3300V/50Hz/RP18TX

7

46-430

70.9

9.79x21.06 (249x535)

1

(2) 500MCM 5kV

or 8kV/phase

(2) 253mm² 5kV

or 8kV/phase

16.4 (415)

PF7000

4160V/50Hz/RP18TX

7

46-430

70.9, 70.18

9.79x21.06 (249x535)

1

(2) 500MCM 5kV

or 8kV/phase

(2) 253mm² 5kV

or 8kV/phase

16.4 (415)

PF7000

4160V/60Hz/RP18TX

7

46-430

70.8, 70.9

9.79x21.06 (249x535)

1

(2) 500MCM 5kV

or 8kV/phase

(2) 253mm² 5kV

or 8kV/phase

16.4 (415)

PF7000

6600V/50Hz/RP18TX

7

40-215

70.9

9.79x21.06 (249x535)

1

(2) 500MCM 8kV

or 15kV/phase

(2) 253mm² 8kV

or 15kV/phase

16.4 (415)

PF7000

6600V/50Hz/RP18TX

7

250-430

70.18

9.79x21.06 (249x535)

1

(2) 500MCM 8kV

or 15kV/phase

(2) 253mm² 8kV

or 15kV/phase

16.4 (415)

PF7000

6600V/60Hz/RP18TX

7

40-215

70.9

9.79x21.06 (249x535)

1

(2) 500MCM 8kV

or 15kV/phase

(2) 253mm² 8kV

or 15kV/phase

16.4 (415)

PF7000

6600V/60Hz/RP18TX

7

250-430

70.18

9.79x21.06 (249x535)

1

(2) 500MCM 8kV

or 15kV/phase

(2) 253mm² 8kV

or 15kV/phase

16.4 (415)

PRODUCT

OUTPUT (MOTOR SIDE)

Bulletin

Description (V/

Freq./Rect.)

Drive

rating

(A)

Drive Structure Code

Drive Enclosure

Opening

Inches (mm)

1

Max. Size & No.

Incoming Cables:

NEMA

2-4-5-6-8-9

Max. Size & No.

Incoming Cables:

IEC

2-4-5-6-8-9

Vertical Space

Avail. for Stress

Cones Inches

(mm)