Chapter 3 Component Definition and Maintenance

• If there have been any changes to the system during the outage, place the

drive in System Test Operating Mode and verify all functional changes.

Final Power Checks (pre-Restart)

• Ensure all cabinets are cleared of tools, and all component connections are

back in place and in the running state.

• Put all equipment in the normal operating mode, and apply medium

voltage.

• If there were any input or output cables removed, verify the input phasing,

and bump the motor for rotation.

• If there were any changes to the motor, input transformer, or associated

cabling, you will have to retune the drive to the new configuration using
Autotuning.

• Save all parameter changes (if any) to NVRAM.
• Run the application up to full speed/full load, or to customer satisfaction.
• Capture the drive variables while running, in the highest access level if

possible.

Additional Preventive Maintenance Tasks

• Investigation of customer’s concerns relating to drive performance

– Relate any problems found during above procedures to customer issues.

• Informal instruction on drive operation and maintenance for plant

maintenance personnel
– Reminder of safety practices and interlocks on MV equipment, and on

specific operating concerns

– Reminder of the need to properly identify operating conditions

• Recommendation for critical spare parts which should be stocked in-plant

to reduce production downtime
– Gather information on all spare parts on site, and compare that with

factory-recommended critical spares to evaluate whether levels are
sufficient.

– Contact MV Spare Parts group for more information.

• Vacuum Bottle Integrity Testing using a Vacuum Checker or AC Hipot

– Refer to Publications 1502-UM050_EN-P (Series D) and 1502-

UM052_-EN-P (Series E) for a detailed description of all 400A
contactor maintenance.

Final Reporting

• A complete, detailed report on all steps in the Preventive Maintenance

procedures should be recorded to identify changes.
– A completed copy of this checklist should be included.