Drive Programming and Parameters Chapter 5
A typical printer screen shows the current printer status and the available report
types. (Refer to the “Syntest SP401 Thermal Printer User Manual” for
information regarding the use of the printer hardware and a description of the
various reports available.) Use
▲
or
▼
to select a report and press [Enter] to send
the report to the printer.
The printer can automatically print out the alarms as they occur if you select this
feature as one of the report formats. In
, the “AUTO - ON” option
indicates this feature is enabled. To disable the alarm printout feature, use
▼
to
select the option and press [Enter]. The option registers “AUTO - OFF” (if a
printer is attached). Pressing [Enter] toggles the option setting.
Perform Diagnostic
Trending
The diagnostic trending operation of screens allows you to capture the
relationships of a number of parameters over a period of time. Within this
operation you will:
• define the parameters to which the trend applies
• define the trigger condition to begin the trend
• define the sampling rate and position of the trigger
• view the results of the trend
Press [F9] to access the DIAGNOSTIC TREND screen from the top-level
menu.
Figure 222 - Diagnostic screen
From this screen, you can perform additional diagnostic trending functions. The
screen shows the current status of the trend (Unprogrammed, Running,
Triggered, Stopped). If there are defined triggers, the trigger parameter, trigger
condition, and the type of trigger also appear.
If the interface has already captured data, the display includes a time stamp
indicating trigger’s last occurrence. View the captured data by pressing [F9].