LED D1 and display U6 indicate the status of the board. The following table
illustrates the possible states for D1.
Table 9 - Status of U6 Display
Replacing the External Input/Output Board
1. Disconnect and lock out all medium voltage and control voltage power to
the drive.
2. Mark the location and orientation of all the plugs, cables, and connectors
into the XIO board. Use the electrical drawing as a reference.
3. Ground your static strap, and disconnect all of the power connections.
4. Remove the XIO board assembly from the low voltage control cabinet.
The XIO board mounts on a DIN rail, so a special 3-piece assembly
secures the board. The assembly does not come with the new board, so you
must remove the old board from the assembly and install the new board in
its place.
5. Install the new XIO board assembly in the low voltage control cabinet.
6. Reconnect all connections and verify the locations.
7. Apply low voltage power and complete both system and medium voltage
tests to ensure the new board functions properly.
LED Status
Description
Solid Green
Normal Operation
Solid Red
Board Failure
Alternate Flashing of Red and Green
No Communication Available to ACB board
(Normal at Power on, during firmware download
and with unprogrammed drive)
Display
Description
Explanation
—
No valid address found
– More than 6 XIO cards on network
– XIO cable failure
– XIO card failure
– ACB failure
0
Card in “Master” mode
– Rockwell Use Only
– Remove connection to J3 and recycle
power
1 – 6
Valid address
Normal
Decimal point ON
Indicates network activity
Normal
Decimal point OFF
No activity on the network
Normal at Power on, during firmware
download and with unprogrammed drive