beautypg.com

Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control (PanelView 550) User Manual

Page 237

background image

Rockwell Automation Publication 7000-UM151E-EN-P - January 2013

237

Drive Programming and Parameters Chapter 5

Starting the Trace

The trend begins as soon as you press [F10], and the interface displays a screen
similar to the example below, show both trigger condition and status. Pressing
[F7] on the DIAGNOSTICS screen may also start the trend.

Figure 226 - Diagnostic armed

Figure 227 - Diagnostic triggered

Once the drive begins collecting data, the diagnostic status shows
‘TRIGGERED’. When the buffer configured for a single trigger contains a
complete capture, the message displays ‘STOPPED’ (see

Figure 228

), along with

the occurrence time and date stamp. The trend buffers are viewable only when
‘STOPPED’.

IMPORTANT The interface does not implement new values until you press [F10] to exit

the screen. Prior to this you can modify the new value by repeating the
above procedure, or cancel by pressing [F7]. Cancelling returns the option
to the original value.