SECTION 6 - JLG CONTROL SYSTEM
3121448
– JLG Lift –
6-51
SETUP 1 - ACCELER
(CALIBRATING TILT SENSOR)
This menu allows the calibration of the tilt sensor.
A NEW TILT MODULE WILL ACT AS IF IT IS TILTED ALL OF THE
TIME UNTIL THE FOLLOWING PROCEDURE IS PERFORMED.
CALIBRATE THE LEVEL SENSOR EXCEPT WITH THE UNITY LEV-
ELED ON BOTH AXLE. CHECK THE BUBBLE LEVEL TO CONFIRM
UNIT IS LEVEL (BUBBLE IS IN THE 1° GREEN (CENTER) AREA).
IF THE BUBBLE IN THE LEVEL IS NOT IN THE GREEN
AREA, EXTEND THE SIDE OUTRIGGERS UNTIL UNIT
IS LEVEL (BUBBLE IS IN THE 1° GREEN (CENTER)
AREA).
Figure 6-21.
1. Engine OFF.
2. Engine Key Switch ON.
3. Press button 6 "SERVICE"
4. Press button 7 "SETUP“
5. Press button 5 “PASSWORD”
Using the remote control buttons to enter the pass-
word 2857.
NOTE: password above allow to calibrate the TILT SENSOR
.
Once the correct password is accepted the display
shown “OK”.
6. Press button 9 “ESC”.
Repeat the above steps if “NO” appear on the dis-
play.
7. Press button 1 “ACCELER” to enter in SETUP TILT
SENSOR.
8. Press Button 1 to reset the TILT.
Check the values if both axle showed in the display
become zero, otherwise press button 1 again until both
values are zero.
Press 3 times button 9 to Esc to escape.