SECTION 6 - JLG CONTROL SYSTEM
3121448
– JLG Lift –
6-13
6.4 CALIBRATION INSTRUCTIONS
This machine incorporates a variety of sensors and a high
degree of function interaction. For safety and proper
machine functionality, the calibration procedures must be
repeated for any control module replacement, system cal-
ibration related fault, or removal or replacement of any
sensors, valves, coils.
The chart below lists the calibrations required and poten-
tial reasons for recalibrating.
All calibration procedures are menu driven through the
REMOTE CONTROL.
The user is prompted to exercise the machine in a specific
order to use the machines physical properties to consis-
tently establish sensor response and the interaction of
valves, pumps, and motors.
A REPLACEMENT ON A NEW ECM 1-2 REQUIRE TO FLASH THE
PROPER MACHINE MODEL SOFTWARE AND TO ADJUST THE
MACHINE SETTINGS. A REPLACEMENT OF A NEW ECM 1-2 DO
NOT REQUIRE THE CALIBRATION OF THE ECM3/ECM4 JOY-
STICKS AND RADIO CONTROL.
Table 6-2. Calibration Instructions
Calibration
Procedure
Reasons for
Re-calibration
LOAD Cell
Calibration
LSS Module ECM3
replacement
LSS Sensor removal or
replacement
Joystick Calibration
Joystick replacement
Chassis Tilt
Calibration
Master Board ECM1- ECM2
removal or replacement
Tilt indication inaccuracy
Rotator Sensors
Calibration
X700AJ X23J Only Board
ECM4 rotator sensor
replacement Rotator sensor
removal or replacement
Radio Control
Calibration
X14HJ X17J Only
Radio Control replacement