7.5.5 Control setting mode (SET 04) (3/4)

Setting data

Character

Setting (monitor) value

Initial value

Unit

Setting

value

Blind

Primary control
operating amount
change limiter ascent

oU1

0.0 to 549.9

0.0

%

Primary control
operating amount
change limiter
descent

od1

0.0 to 549.9

0.0

%

Primary control
soft-start output

SFM

MLL1 to MLH1

100.0

%

Primary control
soft-start time

SFT

00:00 to 499:59
Function turned off with 00:00
(second) setting

000:00

Second

Primary control
at-abnormality
operating amount

FAL1

Digital output: 0.0 to 100.0
Analog output: -10.0 to 110.0

0.0

%

Primary control loop
anomaly PV threshold

tS1

Temperature: 0.0 to 999.9

0 to 999

Analog: 0 to 9999

0

C

Digit

Primary control loop
anomaly MV
threshold

MS1

MLL1 to LH1

100.0

%

Primary control loop
anomaly PV change
threshold

PS1

Temperature: 0.0 to 999.9

0 to 999

Analog: 0 to 9999

0

C

Digit

Primary control loop
abnormality time

LoP1

0 to 9999

0

Second

Primary control
off-point position
selection

CMod

0: SV unit setting
1: Upper
2: Middle
3: Lower

0

None

Primary control
sensitivity setting

C1

Temperature: 0.0 to 999.9

0 to 999

Analog: 0 to 9999

1

Digit

Primary control
off-point position

CP1

Temperature: -999.9 to 999.9

-999 to 999

Analog: -9999 to 9999

0

C

Digit

Primary control
protection off timer

Fdt1

0 to 99

0

Minute

Primary control
protection on timer

Ndt1

0 to 99

0

Minute

Secondary control
operating amount

MV2

MLL2 to MLH2

0.0

%

Secondary control
output gain

MV2G

0.0 to 100.0

100.0

%

Secondary control
proportional band

P2

0.10 to 10.0

1.00

Times

Secondary control
proportional cycle

t2

0.1 to 120.0

20.0

Second

Secondary control
operating amount
limiter upper limit

MLH2

Digital output: MLL2 to 100.0
Analog output: MLL2 to 110.0

100.0

%

Secondary control
operating amount
limiter lower limit

MLL2

Digital output: 0.0 to MLH2
Analog output: -10.0 to MLH2

0.0

%

Secondary control
operating amount
change limiter ascent

oU2

0.0 to 549.9

0.0

%

Secondary control
operating amount
change limiter
descent

od2

0.0 to 549.9

0.0

%

Note

(Ndt1) is selectable only on Ver3.xx or later.