TOHO ELECTRONICS TTM200 User Manual
Page 194
![background image](/manuals/373640/194/background.png)
48-7009-E
6-46
■ Ramp time setting
SEt04
CNt
Setting content
Initial value
57
RMP
Thermocouple/resistance temperature detector input
0.0 to 999.9 (
C/minute)
0.0
Voltage/current input
0 to 9999 (digit/minute)
0
Set the ramp time.
A change of SV per minute is set when SV is changed.
The ramp control starts from the present PV.
(1) At power-on
(2) SV change when bank being switched over
(3) When RDY being switched over to RUN
SV
* Settable at bank setting
The setting value changes from the
temperature at start of the operation to SV,
using the operating amount set for RMP.
SV
RMP
1 minute
Time
At start
Note Event output during ramp
The SV during ramp is equivalent to the SV for deviation upper/lower limit, deviation upper limit, deviation lower limit and
deviation range.
Take care that SV is not a final target value.
Note In the case of ramp setting (RMP = 0), the ramp function does not work.