TOHO ELECTRONICS TTM200 User Manual
Page 135

48-7009-E
5-65
This section introduces the timer function. Timer behavior is determined by defining the following
parameters: timer function setting [tMF 1 to tMF 3], unit setting [H/M 1 to H/M 3], SV start allowable
range setting [tSV 1 to tSV 3], On delay timer [oNt 1 to oNt 3], Off delay timer [oFt 1 to oFt 3],
repetition count setting [RUN 1 to RUN 3], etc.
(Timer function setting)
SEt14
tIME1
to
SEt16
tIME3
Setting content
Initial
value
1
tMF1
to
tMF3
1 Auto start
1
2 Manual start
3 SV start
4 DI 1 start (settable when an option existent)
5 DI 2 start (settable when an option existent)
6 DI 3 start (settable when an option existent)
7 DI 4 start (settable when an option existent)
8 Event 1 start
9 Event 2 start
10 Event 3 start (settable when an option existent)
11 Event 4 start (settable when an option existent)
12 Event 5 start (settable when an option existent)
13 Event 6 start (settable when an option existent)
14 Event 7 start (settable when an option existent)
15 Step start
16 Soak start
(Unit setting)
Setting content
Initial
value
2
H/M1
to
H/M3
1 Hour/minute
1
2 Minute/second
If the SV start is set, set the temperature in
C or the digit width range which a timer starts.
(SV start permissible range setting)
Setting content
Initial
value
3
tSV1
to
tSV3
Thermocouple/resistance temperature detector input
0.0 to 999.9 (
C)
0 to 999 (
C)
0
Voltage/current input
0 to 9999 (digit)
• The allowable range is set in range of tSV with its center at the SV value as illustrated below.
SV value
tSV
• If tSV is set to 1.0
C, the timer becomes active when a temperature falls within the SV value
0.5
C.
Note If the ramp function is also used, tSV is attached to a target SV value.