■ Primary control abnormality operating amount setting
SEt04
CNt
Setting content
Initial value
28
FAL1
Digital output
0.0 to 100.0 (%)
0.0
Analog output
-10.0 to 110.0 (%)
Set the primary control at-abnormality operating amount setting.
This operating amount is the one provided in case of failure of gauges and such.
• Burn-out
• Err 1 (AD abnormality error)
• Err 2 (AT error)
Note
(1) The operating amount is output without constraint from MLH 1 (primary control operating amount limiter upper limit) or
MLL 1 (primary control operating amount limiter lower limit).
(2) Burn-out during the manual control results in outputting the operating amount that is set in MV 1 (primary control
operating amount).
(3) The operating amount cannot be set during the control type of ON/OFF control. (No screen is displayed.)