TOHO ELECTRONICS TTM200 User Manual
Page 209

48-7009-E
6-61
Setting example:
When “AT start” is assigned to DI 1 (close active)
Set dIF to 0005 and dIP to 0000.
When DI is inactive
200
200
200
At
Switch OFF
DI1
Lighting
When DI is active
Switch ON
Usable DIs for each product model
DIs indicated in the table are usable when DI types are optionally designated.
TTM-204
TTM-205
TTM-209
TTM-207
DI1
DI2
DI3
DI4
■ DI polarity setting
SEt13
dI
Setting content
Initial value
2
dIP
****
||||
|||+-- DI 1 setting (settable when an option existent)
||+--- DI 2 setting (settable when an option existent)
|+---- DI 3 setting (settable when an option existent)
+----- DI 4 setting (settable when an option existent)
0000
0
Close active
1
Open active
“Close active” or “open active” is set for “DI function setting” described above.
Close active: DI is active when short (max. 333
) is established between DI terminals.
Open active: DI is active when release (min. 500 k
) is established between DI terminals.