TOHO ELECTRONICS TTM200 User Manual
Page 146

48-7009-E
5-76
■ Setting example 3: Bank automatic switching function setting mode (when the program run function is
also used)
This example shows use of both the program run and eight banks for the bank automatic switching
function. The “designated bank” setting for a program run is ineffective in a bank automatic
switching function run. The bank designation according to the bank automatic switching function is
always prioritized over others.
Note Note that the SET 22 [St1bK to St8bK] step* designated bank setting is not also displayed.
SV
SLH
PM7
PM6
PM5
PM4
PM3
PM2
PM1
SLL
SV
value
PM7≦ SLL≦ PM1≦ PM2≦ PM3≦ PM4≦ PM5≦ PM6≦ SET 20 M a x . 1 6 p a ra m e te rs Max. 8 banks Bank 0 Bank 1 Bank 2 Bank 3 Bank 4 Bank 5 Bank 6 Bank 7 RMP RMP 10 RMP 10 RMP 10 RMP 10 RMP 5 RMP 5 RMP 10 P1 3.0 P1 4.0 P1 4.0 P1 4.0 P1 4.0 P1 2.0 P1 2.0 P1 4.0 I 0 I 20 I 20 I 20 I 20 I 10 I 10 I 20 D 0 D 5 D 5 D 5 D 5 D 2 D 2 D 5 • • • • • • • • • • • • • • • • • • • • • • • • STEP1 STEP2 STEP3 STEP4 STEP5 STEP6 STEP7 STEP8 SV1 50 C SV2 100 C SV3 150 C SV4 200 C SV5 150 C SV6 100 C SV7 150 C SV8 20 C TIM1 00:30 TIM2 00:40 TIM3 00:50 TIM4 01:00 TIM5 00:30 TIM6 00:40 TIM7 00:50 TIM8 02:10 Run start Run stop Zone threshold Temperature change pattern Bank 7 Bank 6 Bank 5 Bank 4 Bank 3 Bank 2 Bank 1 Bank 0 Refer SET 22 setting value Step SV setting Step time setting Step bank setting Max. 8 steps STOP operation Run end Ineffective when the bank automatic switching function is used The designated bank is automatically switched according to the bank automatic switching source
setting value
setting
value.